Retrofit of R-410A in a Water Chiller: Test of Four Low GWP Candidates

Abstract : R-410A is one of the main refrigerants used for air conditioning and heat pump systems. This refrigerant has a high GWP and it is nowadays question of phasing it out (European F-gas directive). In Japan, R-32 is considered as a potential replacement for R-410A (Barve, 2012). This refrigerant permits to reduce the GWP from 2090 kgeq CO2 to 675 kgeq CO2 but presents an issue with the compressor outlet temperature especially in hot climate countries. HFO refrigerants gained attention recently especially with the European mobile air conditioning regulation. These refrigerants have a GWP lower than 10 but have lower volumetric cooling capacity than R-410A and flammability issues. Refrigerant manufacturers are currently developing new refrigerant blends permitting to match heating capacity of R-410A with low GWPs. Within the AHRI AREP initiative, four low GWP candidates for R-410A replacement are tested in a water chiller. This paper presents these test results.
Type de document :
Communication dans un congrès
Liste complète des métadonnées

https://hal-mines-paristech.archives-ouvertes.fr/hal-01462105
Contributeur : Joelle Andrianarijaona <>
Soumis le : mercredi 8 février 2017 - 16:31:46
Dernière modification le : lundi 12 novembre 2018 - 11:01:11

Identifiants

  • HAL Id : hal-01462105, version 1

Collections

Citation

Rani Hanna, Egoi Ortego, Assaad Zoughaib. Retrofit of R-410A in a Water Chiller: Test of Four Low GWP Candidates. 24th IIR International Congress of Refrigeration (ICR 2015), Aug 2015, Yokohama, Japan. ⟨hal-01462105⟩

Partager

Métriques

Consultations de la notice

97